Skip to content
Pillar Page Header Feuerwehrschalter

QFire BIG PV Firefighter Switch for Large PV Systems

Generator-side disconnection of multiple PV strings – project-specifically planned, with galvanic isolation according to IEC 60947-3.

QFire BIG Firefighter Switch Box with 24 Strings and Surge Protection

String-Level Remote DC Disconnection for Large PV Systems

The QFire BIG PV firefighter switch is a string-level, remotely controlled DC isolation solution for commercial and industrial PV systems designed in accordance with IEC requirements. Internationally, this type of solution is also referred to as a Fireman Switch, Firefighter Switch or Emergency Shut-Off System for commercial PV installations.

The system is designed for rooftop PV systems, industrial buildings, logistics roofs and complex photovoltaic installations where multiple PV strings, long DC cable routes or several generator fields need to be disconnected safely.

The QFire BIG switch boxes are installed close to the generator and disconnect the connected PV strings by galvanic isolation according to IEC 60947-3. Depending on the project, up to 24 PV strings can be handled in one switch box. The system is designed to match the installation – taking into account the number of strings, system voltage, string current, roof structure, cable routing and the required shutdown concept.

In addition, QFire BIG can be integrated project-specifically into an AC-side shutdown concept. Via the status contact of the QFire control box, external components such as grid and system protection, inverter enable inputs or site-specific contactor controls can be activated. This allows DC-side PV generator disconnection and AC-side shutdown logic to be planned together for large PV systems.

QFire BIG is not a module optimizer and not a conventional module-level rapid shutdown solution. The focus is not on power optimization at individual module level, but on safe DC string disconnection and PV generator disconnection for professional PV systems – for example in case of fire, during maintenance work or for service operations.

Thanks to the central control box, project-specific DC switch boxes, the optional cluster solution, and external emergency stop connection, QFire BIG can be flexibly integrated into a wide variety of system concepts. The system is particularly suitable for:

QFire BIG at a Glance

ApplicationLarge commercial and industrial PV systems, large rooftop installations, industrial buildings and complex PV systems
FunctionDC string disconnection / PV generator disconnection
DisconnectionGalvanic isolation according to IEC 60947-3
System voltageUp to 1,500 V DC
String currentUp to 20 A Isc per string
Number of strings
Up to 24 PV strings per switch box
ExtensionsEmergency stop, key switch, fire alarm system, status contact, SPD, fuses, cluster, integration into AC-side shutdown concepts

The modular system architecture is particularly suitable for complex roof structures, multiple generator fields, and large PV capacities with many strings. Depending on system size, switching units for 2 to 24 strings are available – with system voltages up to 1,500 V DC and up to 20 A per string.

For extensive sites, multiple QFire systems can be controlled together via the QFire Cluster Control Box. This allows central disconnection of multiple buildings or separate generator fields.

Surge protection, external emergency stop buttons, key switches, status contacts, and online monitoring via QFire.LIVE are optionally available.

PV Firefighter Switch for Large Commercial PV Systems

The QFire BIG PV firefighter switch is a Q3 solution for commercial and industrial PV systems with large numbers of PV strings, long DC cable routes, multiple roof areas or enhanced requirements arising from fire safety concepts, operators, insurers or project specifications.

The switch boxes are installed close to the PV array and provide galvanic isolation of the connected PV strings on the DC side in accordance with IEC 60947-3. This makes QFire BIG particularly suitable for large rooftop PV systems, industrial buildings, public buildings and complex PV installations with system voltages of up to 1,500 V DC.

Shutdown can be triggered on a project-specific basis via the control box, loss of mains supply, an external emergency-stop button, key switch, fire alarm system or external control contacts. Optional features include surge protection, PV fuses, status contacts, sequential shutdown or cluster solutions for multiple roof areas.

Weather-protected installation of multiple QFire Switch Boxes on a commercial flat-roof PV system

QFire BIG in PV System Planning

Which PV firefighter switch is suitable for commercial PV systems?

In commercial and industrial PV systems, a simple DC disconnect switch at the inverter is often not sufficient, especially when long DC cable routes, multiple roof areas or specific requirements from the fire safety concept have to be considered. The key points are where the PV strings are disconnected, which voltages and currents are present, and how the shutdown should be triggered in an emergency.

Read more →

QFire BIG is designed for exactly these types of systems. The switch box is installed close to the PV generator and disconnects the connected PV strings by galvanic isolation according to IEC 60947-3. This allows the DC cables from the switch box towards the inverter to be disconnected in a controlled way – manually via the control box, via external emergency stop or key switches, via a fire alarm system or, depending on the system design, AC-coupled in case of grid failure.

For planners and installers, the important point is this: QFire BIG is not treated as a standard off-the-shelf device, but is configured project-specifically according to the number of strings, roof structure, cable routing, protection concept and required accessories.

What is needed for DC string disconnection in large PV systems?

In large PV systems, DC string disconnection should be considered early in the planning phase. The most relevant factors are the maximum DC system voltage, the short-circuit current per string, the number of strings, the allocation to MPPTs, the cable routes from the PV generator to the inverter and the requirements from the fire safety concept.

Read more →

QFire BIG is configured precisely for these conditions. Depending on the project, several strings can be combined in one switch box and disconnected close to the generator. Optional components such as surge protection, PV fuses, status contacts, external shutdown points or cluster solutions for multiple roof areas can be integrated.

The aim is not to place as many components as possible somewhere in the system, but to create a clear and serviceable DC structure: traceable string routing, a defined disconnection point, clear status indication and a solution that fits the actual PV system.

How can multiple PV strings be disconnected safely?

Multiple PV strings are best disconnected at the point where they are routed from the generator towards the building or inverter. This is exactly where QFire BIG is used. The switch box is installed close to the generator and disconnects the connected DC string cables by galvanic isolation.

Read more →

Depending on the configuration, several PV strings can be handled in one QFire BIG switch box. This makes it possible to create a structured shutdown concept even for larger rooftop systems, without having to treat every single string with a separate standalone solution. Operation is carried out centrally via the control box or via integrated external shutdown points.

For large systems with several building sections or roof areas, the shutdown concept can also be planned using cluster technology. This keeps operation clear and manageable, even when the DC structure of the PV system is more complex.

Combining DC and AC shutdown in the system concept

Modular PV Array Disconnection System for Large PV Installations

QFire BIG enables galvanic isolation of PV strings between the generator field and inverter. Typical components are:

The QFire BIG system has a modular design and consists of a central control box, optional cluster control boxes, and DC switch boxes for up to 24 strings per box. The switch boxes are custom-built and can optionally be equipped with surge protection and fuses.

Optional components are:

■ Fire alarm system connection
■ Integrated surge protection
■ Integrated fuses in positive and/or negative pole
■ External emergency stop button
■ Cluster technology for multiple roof areas
■ Online monitoring
■ Delay circuit (time-delayed disconnection of large systems)

Structure of the QFire PV Firefighter Safety Switch System
Cluster Steuerbox für mehrere Generatorflächen
Technische Details

Central Control and Coordinated Disconnection of PV Strings

Cluster Steuerbox für mehrere Generatorflächen
Technische Details

Additionally: Higher-Level, Star-Configured Disconnection Structure

Technische Details

Optional Surge Protection for the QFire Control Line

Technical Data:

The values shown correspond to the data sheet of the surge protective device used.

An optional surge protection device is available for the 24 V DC control and signalling cable of the QFire BIG system.

The protection module is integrated into the QFire switch box at Q3 and protects the control cable against transient overvoltages and surge currents.

The multi-stage protection concept, comprising a gas discharge tube, series resistor and clamping diode, provides high discharge capacity with a low voltage protection level. The protection module is replaceable, so the complete QFire switch box does not need to be replaced if the protective component is damaged.

QFire Ueberspannungsschutz fuer Steuerleitungen 800 px edited

Important for Systems with Multiple QFire Switch Boxes

The surge protection device is integrated into the first switch box of the QFire BIG system. This box is marked “1” by Q3.

For systems with multiple switch boxes, the first switch box must therefore be specified when placing the order, unless this is already clearly defined in the project design.

Technische Details

How does the QFire BIG differ from Module Optimizers and Rapid Shutdown Systems?

QFire BIG is not a module optimizer solution and not a conventional module-level rapid shutdown solution. This distinction is important because these systems follow a different technical approach.

Module optimizers, microinverters and MLPE systems operate directly at the individual module or module string and are often associated with power optimization, monitoring or rapid shutdown. QFire BIG is designed differently: the system disconnects PV strings close to the generator via a switch box and is designed for commercial and industrial PV systems with multiple strings, clear cable routing and a defined shutdown concept.

The focus is not on module optimization, but on safe DC string disconnection and PV generator disconnection. QFire BIG disconnects the DC strings by galvanic isolation according to IEC 60947-3 and is integrated into the project-specific system planning.

Number of Strings
DC surge protection
Technische Details
Anfrage
Inquiry
PDF
PDF icon for QFire firefighter switch technical documentation
Wann ist bei einer PV Anlage ein Feuerwehrschalter Pflicht?
When is a firefighter switch mandatory for a PV system?
FAQ Feuerwehrschalter
Firefighter Switch FAQ

QFire BIG PV Firefighter Switch in Large-Scale PV System Design

Which DC Firefighter Switch Is Suitable for Large Commercial Rooftop PV Systems at 1,500 V DC?

For large commercial rooftop PV systems, the firefighter switch must be matched to the system architecture. Key factors include the number of PV strings, DC system voltage, short-circuit current per string, roof areas, cable routing and the required shutdown concept.
QFire BIG has been developed for larger commercial and industrial PV systems. The switch boxes are installed close to the PV array and provide galvanic isolation of the connected PV strings on the DC side in accordance with IEC 60947-3. QFire BIG is therefore particularly suitable for systems with large numbers of strings, long DC cable routes, multiple roof areas or enhanced requirements arising from fire safety concepts, operators, insurers or project specifications.

QFire BIG is Q3’s project-specific PV firefighter switch for large commercial and industrial PV systems with multiple strings, long DC cable routes, multiple roof areas and galvanic isolation close to the PV array in accordance with IEC 60947-3.

When Is QFire BIG the Right Solution Instead of QFire LITE?

QFire LITE is designed for smaller PV systems with only a few strings. QFire BIG is used where larger numbers of strings, larger roof areas, more complex cable routes or additional options are required.
Typical applications for QFire BIG include commercial rooftop PV systems, industrial buildings, public buildings, logistics facilities and larger PV systems with multiple PV arrays. Depending on the project, each switch box can accommodate up to 24 PV strings. Optional features include surge protection, PV fuses, status contacts, external emergency-stop switches, key switches, integration with a fire alarm system and cluster solutions.

Where Should a PV Firefighter Switch Be Installed in a Large PV System?

A PV firefighter switch should be designed so that the DC circuits can be safely and clearly isolated when a shutdown is triggered. With QFire BIG, the DC switch boxes are installed close to the PV array. This allows the PV strings to be isolated before long DC cable routes continue towards the inverter or enter the building.
The exact installation location depends on the overall system design. Roof structure, string routing, inverter position, cable routes, fire safety requirements and accessibility must all be considered. QFire BIG is therefore designed on a project-specific basis rather than installed as a standard box in a predefined location.

How Does DC String Shutdown Work with QFire BIG?

QFire BIG disconnects PV strings on the DC side at a defined switching point. The connected strings are galvanically isolated close to the PV array in accordance with IEC 60947-3. Depending on the project, shutdown can be triggered via the QFire control box, loss of mains supply, an external emergency-stop switch, key switch, fire alarm system or external control contacts.
QFire BIG is based on string-level DC shutdown and PV array disconnection. It is not a module optimiser, microinverter system or conventional module-level rapid shutdown solution. The system is designed for professional PV installations with a clearly defined string architecture and a project-specific shutdown concept.

What Is the Difference Between a Firefighter Switch, DC Switch-Disconnector and PV Array Disconnection?

A DC switch-disconnector generally provides a switching and isolation function on the DC side of a PV system. A PV firefighter switch is a project-specific shutdown solution designed to isolate DC circuits for emergency response, maintenance or other safety-related situations.
PV array disconnection means isolating the PV array, or the connected PV strings, from the downstream DC cabling. QFire BIG combines these functions within one system: the switch boxes provide galvanic isolation of the PV strings close to the array, while the control box provides the shutdown logic and interfaces for external triggering devices.

Is a Firefighter Switch Mandatory for Commercial PV Systems?

There is no general legal requirement that applies to every PV system. In practice, however, a firefighter switch may be required or strongly recommended by the fire safety concept, project specification, system operator, insurer, fire and rescue service or regional requirements.
Particularly for commercial rooftop PV systems, public buildings, industrial facilities, multiple roof areas or long DC cable routes, PV array disconnection should be considered at an early stage of the design process. QFire BIG is configured on a project-specific basis to ensure that the technical requirements, system architecture and shutdown concept are properly coordinated.

Can QFire BIG Be Triggered by a Fire Alarm System, Emergency-Stop Switch or Key Switch?

Yes. QFire BIG can be configured with different triggering methods to suit the project. These include external emergency-stop push-buttons, key switches, fire alarm systems, loss of mains supply and external control contacts.
The appropriate triggering method depends on the safety concept of the installation. For public buildings, industrial projects or systems with specific safety requirements, integration with a fire alarm system or central emergency-stop concept may be appropriate.

What Information Is Required to Design a QFire BIG PV Firefighter Switch?

Project-specific design requires the key technical data of the PV system. This includes the number of strings, maximum DC system voltage, short-circuit current per string, number and allocation of MPP trackers, inverter location, roof areas, cable routing and the required connection technology.
It is also important to know whether surge protection, PV fuses, status contacts, emergency-stop switches, key switches, integration with a fire alarm system, sequential shutdown or a cluster solution are required. This information is used to determine the appropriate QFire BIG configuration for the system.

How Much Does a Firefighter Switch for a Large PV System Cost?

The cost of a firefighter switch for a large PV system depends heavily on the technical configuration. Key factors include the number of strings, system voltage, string current, enclosure size, connection technology, surge protection, PV fuses, control system, status signalling, triggering method and any additional functions required.
For commercial and industrial PV systems, the firefighter switch should therefore be considered as part of the overall DC shutdown and protection concept rather than as an isolated component. Q3 ENERGIE designs QFire BIG on a project-specific basis and determines which solution is technically appropriate and economically suitable.

Can QFire BIG Be Used as an Emergency-Stop or Emergency Shut-Off Solution?

Yes. QFire BIG can be integrated into a project-specific emergency-stop or firefighter shutdown concept for commercial and industrial PV systems. Depending on the configuration, shutdown can be triggered via the QFire control box, loss of mains supply, an external emergency-stop push-button, key switch, fire alarm system or external control contacts.
Internationally, this type of solution is commonly referred to as a Fireman Switch, Firefighter Switch or Emergency Shut-Off Switch for PV systems. QFire BIG is technically focused on DC string shutdown close to the PV array and galvanic isolation of the connected PV strings in accordance with IEC 60947-3.

String-Level DC Shutdown or Module-Level Shutdown: Which Solution Is Suitable for Commercial PV Systems?

Module-level shutdown reduces the voltage very close to the PV module, but also introduces additional electronics, additional connection points and more components on the roof.

String-level DC shutdown operates at defined isolation points and can provide a robust, maintenance-friendly and clearly documented safety architecture for commercial PV systems – particularly where there are large numbers of strings, long cable routes, 1,500 V DC systems or project-specific fire safety requirements.

Presse